Home ] Basements ] Book Pricing ] Complaints ] Contractors ] Decks ] [ Designs ] Enumerations ] Floodplain ] Inspections ] Insurance ] Legal & Liens ] MfgHome ] Misc. ] Monolithic ] Performance ] Permits ] Phone List ] Plan Check ] Plot/Site Plans ] Rescinds ] Roofing ] Shed Info ] Soil Report ] Temp CO ] Trees ] Trip Fees ] Variances ] Zoning ]

The 2005 Pikes Peak Regional Building Code amends the 2003 International Building Code and can be purchased from the Regional Building or downloaded at www.pprbd.org.

Design Code: 2005 PPRBC & 2003 IBC

Frost Line: 30"

Snow Loads:
    For below 7000: 30 psf uniform
    At or above 7000: 40 psf uniform
        (additional questions regarding grade plane and related
        snow load or flat roof snow load should be referred to plan check)

Wind Loads:
    Basic wind speed: 100 mph (3 second gust)
    Exposure C
    Minimum Wind Load: 20 psf
        (PPRBC requires a 20 psf minimum wind load where the IBC
        requires a 10 psf minimum. Additional questions regarding
        wind load should be referred to plan check)

Live and Dead Loads:
    Dead loads and live loads shall be prescribed per the 2003 IBC.
    See RBC302.4.55 for specific amendments. (Refer questions to
    Plan Check)